테크놀로지

㈜써지프리는 서지보호와 전기품질 분야에서 우수하고
안전한 제품과 솔루션을 공급합니다.

기술자료

UL 1449 5th Edition and IEC 61643 both cover the safety and performance of SPD

UL 1449 5th Edition and IEC 61643 are both representative international standards for the safety and performance of surge protection devices (SPDs). The main differences between each standard, including focus, classification method, and test method, are summarized below.

Classification method

  • UL 1449 5th Edition : Classifies SPDs into Type 1, 2, 3, 4, and 5 according to installation location (e.g. transformer secondary side, distribution board, terminal, etc.). Focuses on the product installation environment and safety.

  • IEC 61643 : Classified into Class I (for direct lightning strikes), Class II (for distribution protection), and Class III (for terminal equipment protection) according to the experimental waveform (e.g. 8/20μs, 10/350μs). Surge protection performance is the main criterion.

Key items for evaluation and testing

division

UL 1449 5th Edition

IEC 61643

Main focus

Numerous product safety, case, and disconnector tests

Surge protection performance (withstands high energy surges)

Classification criteria

Installation location (Type 1, 2, 3, 4, 5)

Experimental waveforms (Class I, II, III)

Test waveform

1.2/50μs & 8/20μs combination waveforms

Class I (10/350μs), II (8/20μs), etc.

Protection class

Voltage Protection Rating (VPR)

Up (Voltage Protection Level)

Rated Items

MCOV (Maximum Continuous Operating Voltage), etc.

Up, In (rated discharge current), Iimp (impulse current), etc.

Test method

Repeated testing with many samples, multiple tests on the disconnector, relatively low surge levels

More surge waveforms, higher surge current values, and more repetitive surge tests

etc

Focused on North America, emphasizing product safety

International (especially European) focused, with an emphasis on performance and durability

Summary of Standard Differentiators

  • UL 1449 places a lot of emphasis on the safety of the device and its suitability for the installation environment (overheating, short circuit, durability, etc.).

  • IEC 61643 places emphasis on the rigor of protective performance under actual lightning/surge conditions and repeated high-energy testing.

  • Both standards test SPDs to ensure they are compatible with each country's utility equipment, but the testing methods and focus are different.