테크놀로지

㈜써지프리는 서지보호와 전기품질 분야에서 우수하고
안전한 제품과 솔루션을 공급합니다.

기술자료

Overcurrent protection function for SPD disconnectors

​Abstract:

A thermal protection function (thermal disconnector) is usually built into voltage clamping-type surge protective devices (SPDs) such as metal oxide varistors (MOVs) for electric power. In addition, if excess voltage or degradation of an SPD causes a large fault current flow, an overcurrent protection function (current disconnector) is used. Thermal disconnectors and current disconnectors are collectively known as SPD disconnectors. IEC 61643-1 specifies the operation of SPD disconnectors when the AC current flowing to an SPD due to degradation failure is below 1A. In such cases, the operation of the thermal disconnector is usually checked. However, there is no concrete examination standard for the shut-off characteristics of a current disconnector. As for thermal disconnectors and current disconnectors, it is desirable that they both perform the shut-off operation and maintain proper functioning. In this study, we describe the operations of thermal and current disconnectors as they relate to SPD safety, with a particular focus on SPD failure causing a fault current exceeding 1A (AC) to flow to the SPD. We used a current fuse uniquely developed at our company and a circuit-breaker (MCCB) that is generally recommended by SPD manufacturers for the current disconnectors. The results of our investigation led us to propose a suitable shut-off characteristic for current disconnectors.  From IEEE 2011 7th Asia-Pacific International Conference on Lightning

먼저 비밀번호를 입력하여 주세요.

창닫기확인